There are analog inputs for 0—20 mA, 0—5 V and 0—10 V field signals. These
field signals can be converted to the required input voltage of the input modules
(such as 0—2 V or 0—4 V) by using an FTA or an input converter module.
Input modules have galvanic isolation between 5 Vdc circuitry and field inputs.
They are fitted with a male connector according to DIN 41612, type F, with the d,
(b) and z rows in use.
The following items terminate on the chassis connector:
? 5 Vdc internal power supply
? 24 Vdc or 48 Vdc internal power supply
? 24 Vdc or 48 Vdc external power supply (if needed)
? Wiring for the input signals
The 5 Vdc signals are physically separated from the IO connections and supply.
The following DC supply voltage ranges apply to ensure correct operation of the
Safety Manager modules:
? 110 Vdc: +25% / –15%
? 48 Vdc: +15% / –15%
? 24 Vdc: +30% / –15%
Notes:
1. If it cannot be guaranteed that the DC power supplied to Safety Manager remains
within the above ranges, additional voltage monitoring is required.
2. It is assumed that the 24Vdc Plant power fed to the SM Controller is uninterrupted. If
not, means should be provided to avoid power dips at the 24Vdc lines to the
SM Controller.
3. When using Plant power, the Plant power supply must fulfill the requirements as laid
down in IEC 61010 or IEC 60950.
Input modules can be replaced with power switched on. Depending on the input
signal function and the system IO configuration, process operation may be
affected.
When removing an input module, first disconnect the flat cable from the
horizontal IO bus (IOBUS-HBS or IOBUS-HBR), loosen the screws, and
carefully slide the module out of the chassis.
When placing an input module into the chassis, carefully push it into the slot until
it is flush with the chassis, fasten the screws, then connect the flatcable to the
horizontal IO bus (IOBUS-HBS or IOBUS-HBR)