本特利Bently監(jiān)測器儀表框架3500/05-01-02-00-00-01系統(tǒng)
本特利Bently監(jiān)測器儀表框架3500/05-01-02-00-00-01系統(tǒng)
分類:?Bently本特利
型號: 3500/05-01-02-00-00-01
產(chǎn)品細節(jié): 3500/05-01-02-00-00-01 3500/05系統(tǒng)機架 繞過所有其他配置的通道
制造商:本特利
產(chǎn)品編號:3500/05-01-02-00-00-01
產(chǎn)品型號:3500/05系統(tǒng)機架
美國制造
機架尺寸:01 = 19英寸機架14個模塊插槽)
安裝選項:02 =機架安裝選項,全尺寸機架(安裝到19英寸EIA機架)
代理審批選項:00 =無
保留:00 =無
歐洲合規(guī)選項:01 = CE
尺寸(長x亮x高):48.26厘米x 34.92cm厘米x 26.59cm厘米
裝運重量:4.5千克
3500/05-01-01-00-00-00測試0K極限的一般方法是輸入直流電壓并進行調(diào)整高于0K上限且低于0K下限,此電壓將導致非OK狀態(tài),OK繼電器改變狀態(tài)(斷電)。鞋面和OK下限顯示在測試的Verification (驗證) 屏幕中計算機
1.從上的通道端子斷開PWR、COM/-和SIG/+現(xiàn)場接線超速檢測輸入/輸出模塊。
2.按照第5.1.5.1節(jié)(測試設備和軟件設置-超速檢測系統(tǒng))。
3.繞過所有其他配置的通道
4.將電源電壓調(diào)整至-10.00 Vdc.
5,通過短路上的復位觸點來復位超速檢測模塊超速輸入/輸出模塊或啟用通道復位軟件開關,驗證監(jiān)視器OK指示亮起,并且verification (驗證)屏墓的Channel Status (通道狀態(tài)) 組顯示OK (正常)?
6.驗證機架接口VO模塊上的OK(正常) 繼電器是否指示OK(正常(通電) ,參見3500/20機架接口模塊操作和維護手冊,件號129768-01.

Product details: 3500/05-01-02-00-00-01 3500/05 system rack bypasses all other configured channels
Manufacturer: Bentley
Product number: 3500/05-01-02-00-00-01
Product Model: 3500/05 System Rack
Made in the United States
Rack size: 01=19 inch rack with 14 module slots)
Installation option: 02=rack installation option, full size rack (installed into a 19 inch EIA rack)
Proxy approval option: 00=none
Reserved: 00=None
European Compliance Option: 01=CE
Dimensions (length x brightness x height): 48.26 cm x 34.92cm x 26.59cm
Shipping weight: 4.5 kilograms
The general method for testing the 0K limit of 3500/05-01-01-00-00 is to input a DC voltage and adjust it to be higher than the 0K upper limit and lower than the 0K lower limit. This voltage will cause a non OK state and the OK relay to change state (power off). The upper and OK lower limits are displayed on the Verification screen of the test computer
1. Disconnect the PWR, COM/-, and SIG/+field wiring overspeed detection input/output modules from the channel terminals on the.
2. According to section 5.1.5.1 (Test Equipment and Software Settings - Overspeed Detection System).
3. Bypass all other configured channels
4. Adjust the power supply voltage to -10.00 Vdc
5. Reset the overspeed detection module overspeed input/output module or enable the channel reset software switch through the reset contact on the short circuit. Verify that the OK indicator on the monitor lights up and that the Channel Status group on the verification screen displays OK
6. Verify that the OK relay on the rack interface VO module indicates OK (powered on), refer to the 3500/20 Rack Interface Module Operation and Maintenance Manual, part number 129768-01