[VPLEX]開關機步驟
開關機的基本順序:
開機: 光纖交換機――存儲設備――VPLEX――主機系統(tǒng)
關機: 主機系統(tǒng)――VPLEX ――存儲設備――光纖交換機
?
關機操作
1.關閉cluster-1上的軟件
1.鍵入以下命令關閉cluster1中的軟件:
VPlexcli:> cluster shutdown --cluster cluster-1
Warning: Shutting down a VPlex cluster may cause data unavailability.? Please refer to the VPlex documentation for the
recommended procedure for shutting down a cluster. To show that you understand the impact, enter 'shutdown': shutdown
?
You have chosen to shutdown 'cluster-1'.? To confirm, enter 'cluster-1': cluster-1??
?
Status??? Description
--------? -----------------
Started.? Shutdown started.
?
說明:系統(tǒng)需要大約3-5分鐘才能關閉.
2.顯示集群狀態(tài)的命令如下,在輸出中,確認集群1的操作狀態(tài)沒有運行。
VPlexcli:/> cluster status
Cluster cluster-1
??????? operational-status:??????? not-running
??????? transitioning-indications:
??????? transitioning-progress:???
??????? health-state:????????????? unknown
??????? health-indications:???????
??????? local-com:???????????????? failed to validate local-com: Firmware command error.
communication error recently.
?
2.關閉集群-1上的控制器和可選的COM開關
1.輸入exit,退出vplexcli模式,輸入以下命令關閉director 1-1-1-A:
ssh -l root 128.221.252.35
shutdown –P “now”
輸出如下:
director-1-1-a:~ # shutdown -P "now"
Broadcast message from root (pts/0) (Fri Nov 18 20:04:33 2011):
The system is going down to maintenance mode NOW!
重復步驟關閉集群其他控制器

ping –b 128.221.252.35
注意:一個控制器可能需要4分鐘的時間來完全關閉。
輸出如下:
PING 128.221.252.35 (128.221.252.35) 56(84) bytes of data.
From 128.221.252.33 icmp_seq=1 Destination Host Unreachable
From 128.221.252.33 icmp_seq=2 Destination Host Unreachable
重復ping其他控制器,確認關閉
2.如果集群只有一個引擎,則跳到任務3:“關閉管理服務器”。
3.如果集群有多個引擎,請按照以下步驟關閉Fibre Channel COM交換機:
輸入以下命令連接到交換機A:
telnet 128.221.252.34
使用用戶名service登錄。
在交換機的命令行,鍵入以下命令關閉開關:
sysshutdown
輸出如下:
--------------------------------------------------------------
FC-Switch-A:service> sysshutdown
This command will shutdown the operating systems on your switch.
You are required to power-cycle the switch in order to restore operation.
Are you sure you want to shutdown the switch [y/n]?y
輸入y,在提示處按回車鍵。
Broadcast message from root (pts/0) Fri Nov 18 20:09:11 2011...
?
The system is going down for system halt NOW !!
FC-Switch-A:service> Connection closed by foreign host.
輸入exit命令終止切換會話,輸入以下命令到ping開關A:
ping –b 128.221.252.34
使用想通方法關閉交換機B,IP地址更換為128.221.253.34
3.關閉cluster-1的管理服務器
VPLEX VS2:
鍵入以下命令關閉cluster-1上的管理服務器:
sudo /sbin/shutdown 0
輸出如下:
Broadcast message from root (pts/1) (Tue Feb 8 18:12:30 2010):
The system is going down to maintenance mode NOW!
?
VPLEX VS6
關閉MMCS-B
使用ssh登陸到MMCS-B
ssh service@128.221.253.33
執(zhí)行關機命令
sudo /sbin/shutdown 0
輸出如下
Broadcast message from root (pts/1) (Tue Feb 8 18:12:30 2010):
The system is going down to maintenance mode NOW!
然后以輸入關閉命令關閉MMCS-A
sudo /sbin/shutdown 0
輸出如下
Broadcast message from root (pts/1) (Tue Feb 8 18:12:30 2010):
The system is going down to maintenance mode NOW!
?
4移除電源線
將所連接電源線全部移除
?
開機操作
? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ?
1.?????? 檢查所有供電線路聯(lián)接是否正常,是否有松動或改動并改正。
2.?????? 打開vplex mamagement server 的電源開關。
3.?????? 打開機柜最底部兩個vplex電池的開關,完成開機。