ABB PM645B Advant控制器70通信接口

2023-04-07 10:08 作者:文武雙全何15859219118  | 我要投稿

當(dāng)將CI520/CI522/CI526連接到總線時(shí),通信接口連接到

帶有調(diào)制解調(diào)器電纜TK515/TK593/TK803的TC512調(diào)制解調(diào)器。帶有集成調(diào)制解調(diào)器的單元

直接連接到總線電纜。

當(dāng)使用單一介質(zhì)時(shí),總線電纜必須連接到Advant上的線路1連接器

控制器70(PM810)和S800 I/O站(CI810)。

調(diào)制解調(diào)器下方應(yīng)留有足夠的空間,以允許一定的最小彎曲半徑

電纜(上圖中的R)。此半徑取決于電纜類型,通常

100毫米用于設(shè)備電纜和室內(nèi)工業(yè)環(huán)境的電纜。用于地下和

通常需要半徑等于或大于200mm(≈8“)的海底電纜。

如果出現(xiàn)不確定性,應(yīng)聯(lián)系電纜制造商。

請(qǐng)聯(lián)系光纜制造商,了解如何在

安裝在電纜上安裝光學(xué)連接器是一項(xiàng)精密的工作,應(yīng)

由專家執(zhí)行。電纜供應(yīng)商通??梢酝扑]此類專家。

光學(xué)連接器為STx4型。

當(dāng)Advant控制器70通信接口被啟動(dòng)時(shí),其CDP被配置。

由于通信接口不能是總線管理員,因此在

當(dāng)前為主的總線管理員。當(dāng)Advant控制器70

啟動(dòng)并連接到總線,或者當(dāng)配置為主控的總線管理員

起動(dòng)。

在啟動(dòng)時(shí),Advant控制器70前部的所有LED在

硬件初始化。

當(dāng)R(RUN)指示燈點(diǎn)亮?xí)r,工作站正在運(yùn)行。

車站地址

在啟動(dòng)Advant控制器70之前,必須為其分配一個(gè)站號(hào)。

通過(guò)PM810前面的地址開(kāi)關(guān)來(lái)選擇電臺(tái)編號(hào)。車站

數(shù)字必須在1到79之間。請(qǐng)參閱Advant Controller 70文檔

以獲取更多信息。

車站地址與公交車沿線車站的順序無(wú)關(guān)。他們只是

表示用于指代特定站點(diǎn)的物理地址。

Advant控制器站號(hào)用作通信的硬件地址

Advant現(xiàn)場(chǎng)總線100上的接口。

When connecting a CI520/CI522/CI526 to the bus the communication interface is connected to

the TC512 modem with modem cable TK515/TK593/TK803. Units with integrated modems are

connected directly to the bus cable.

When single media is used the bus cable must be connected to the Line 1 connector on Advant

Controller 70 (PM810) and S800 I/O Station (CI810).

Sufficient space should remain beneath the modem to permit a certain minimum bending radius

of the cable (R in the figure above). This radius depends on the cable type and is normally

100 mm for apparatus cable and cable for indoor industrial environments. For underground and

submarine cable, a radius equal to or greater than 200 mm (≈ 8”) is normally required.

The manufacturer of the cable should be contacted in the event of uncertainty.

Contact the optical cable manufacturer about info how to handle the optical cable during

installation. The installation of optical connectors on the cable is a precision work which should

be performed by specialists. The cable supplier can usually recommend such experts.

The optical connectors are of the STx4 type.

When an Advant Controller 70 communication interface is started, its CDPs are be configured.

As the communication interface can not be a Bus Administrator, its CDPs are configured on the

Bus Administrator which currently is master. This is performed when the Advant Controller 70

is started and connected to the bus or when a Bus Administrator configured as master has

started.

At start up all LEDs on the Advant Controller 70 front are lit for about a second during the

hardware init.

The station is running when the R (RUN) indicator is lit.

tation Address

Before starting the Advant Controller 70, it must have been assigned a station number.

The station number is selected with the address switches on the PM810 front. The station

number must be in the range of 1 to 79. Please refer to the Advant Controller 70 documentation

for further information.

The station address has no relation to the order of the stations along the bus. They merely

represent physical addresses which are used to refer to specific stations.

The Advant Controller station number acts as the hardware address of the communication

interface on the Advant Fieldbus 100.?