these fields if the time stamp received from the INSUM device is incorrect. (See
below).
Generating Alarms for Alarm Lists
The controller system software generates alarms for the alarm and event lists in the
system, based on the updates of the INSUM alarm information if the parameter
Generate Alarms on the device is set to Enabled or Enabled Trip/Warning or
Enabled Detailed.
If the time stamp received from the INSUM device is correct (a valid time) this time
stamp is used for the generated alarm message. If it is not, the system software tags
the generated alarm message with the current controller time.
In this case, the alarm messages are time stamped in the controller. If this time
accuracy is sufficient, this method is probably to be recommended because it is
easier to configure. No System Clock is needed in the INSUM system. If you let the
system software generate the alarms it can use the time stamp given by the INSUM
devices. If the INSUM System Clock is used this is a much more accurate time
stamp.
Summary Alarms, One Alarm Object Per Device
Generate Alarms = Enabled means that the system software internally (without
needing INSUMReceive) creates a subscription of the alarm variable from the
INSUM device. When this variable is updated from the INSUM system, the system
software evaluates the content.
If a bit (one or more) which is classified as an alarm (e.g. not the bit "Started1") is
set and no such bit previously was set, the system software generates one alarm
message.
If an alarm update is received with the change that no alarm classified bits are set
any more, the system software generates the alarm-off message