ABB 3BHE024747R0101 參考數(shù)據(jù)集和輔助參考數(shù)據(jù)


基板具有鎖定機(jī)構(gòu),該鎖定機(jī)構(gòu)將金屬背板連接到
DIN導(dǎo)軌,提供有效的接地連接。
1.將鎖定裝置旋轉(zhuǎn)到打開位置。鉤住后部的上唇
在DIN導(dǎo)軌的上邊緣上方固定基板,然后卡扣基板
完全進(jìn)入安裝位置。
2.將鎖定裝置旋轉(zhuǎn)到滑動(dòng)位置。沿著DIN滑動(dòng)裝置
導(dǎo)軌到所需的安裝位置,并將其連接到相鄰的單元底板
帶有連接器插頭和插座。
3.將鎖定裝置順時(shí)針旋轉(zhuǎn)至鎖定位置。
ACS800標(biāo)準(zhǔn)應(yīng)用程序7.x支持使用四個(gè)數(shù)據(jù)集,
每個(gè)方向兩個(gè)。
用于控制驅(qū)動(dòng)器的兩個(gè)數(shù)據(jù)集被稱為主參考
數(shù)據(jù)集和輔助參考數(shù)據(jù)集。驅(qū)動(dòng)器讀取的源
主參考數(shù)據(jù)集和輔助參考數(shù)據(jù)集由參數(shù)90.04和
分別為90.05。主參考數(shù)據(jù)集的內(nèi)容是固定的。這個(gè)
可以使用參數(shù)90.01來選擇輔助參考數(shù)據(jù)集的內(nèi)容,
90.02和90.03。
包含驅(qū)動(dòng)器實(shí)際信息的兩個(gè)數(shù)據(jù)集稱為
主實(shí)際信號(hào)數(shù)據(jù)集和輔助實(shí)際信號(hào)數(shù)據(jù)集中。的內(nèi)容
兩個(gè)數(shù)據(jù)集都是部分可選擇的,并且具有組92處的參數(shù)。
通過設(shè)置參數(shù)98.02 COMM.MODULE LINK(通信模塊鏈接)激活外部控制
給ADVANT。

The base plate has a locking mechanism that connects the metallic back plate to the
DIN rail, providing an effective ground connection.
1. Rotate the locking device to the OPEN position. Hook the upper lip at the rear
of the base plate over the upper edge of the DIN rail and snap the base plate
fully into the mounting position.
2. Rotate the locking device to the SLIDE position. Slide the unit along the DIN
rail to the desired mounting position and attach it to the adjacent unit base plate
with the connector plugs and sockets.
3. Rotate the locking device clockwise to the LOCKED position.
The ACS800 Standard Application Program 7.x supports the use of four datasets,
two in each direction.
The two datasets for controlling the drive are referred to as the Main Reference
dataset and the Auxiliary Reference dataset. The sources from which the drive reads
the Main and Auxiliary Reference datasets are defined by parameters 90.04 and
90.05 respectively. The contents of the Main Reference dataset are fixed. The
contents of the Auxiliary Reference dataset can be selected using parameters 90.01,
90.02 and 90.03.
The two datasets containing actual information on the drive are referred to as the
Main Actual Signal dataset and the Auxiliary Actual Signal dataset. The contents of
both datasets are partly selectable with the parameters at group 92.
External control is activated by setting parameter 98.02 COMM. MODULE LINK
to ADVANT.